DC IT Room Quartzite 9.0 Grafic

DC IT Room
Quartzite 9.0

Basic protection for your data center

  • Modular room-in-room system consisting of wall, ceiling and floor elements
  • Structural IT protection according to BITKOM RZ category A
  • Basic protection for IT against the main physical hazards (fire, burglary, water, dust, EMC electromagnetic compatibility...)
  • System-tested fire protection EI 90 based on EN 1363.
  • network--1
    Service-friendly & innovative cable and pipe bulkhead system
Configure now

Modular room-in-room system with basic protection against the main physical hazards

The DC IT Room Quartzite 9.0 is a perfect modular room-in-room solution with basic protection against the main physical hazards. The installation is simple and completely modular and the solution is adapted to dimensions of the room and customer specifications.

The solution is used for the protection of the IT room and optionally protection of the technical room or also as a separation between IT room and technical room.

Detail photos DC IT Room Quartzite 9.0

Climate slider, a white rectangle with mesh
Cable outputs in different colors and 2 brass outputs
Fire damper, shelf with regulator in front
open door, behind server's desk
open door, behind server's desk
door knob with lock

Basic protection against physical hazards

Fire protection

Burglary protection

Explosion protection

Water and dust protection

Protection from debris load

Protection against vandalism

mobile-data
Protection from radiation

hearing
Noise protection

Protection against corrosive gases

Modular design: can be disassembled, reassembled and extended

The flexible, modular room system is expandable from 2 m² up to a large-scale data center. The system adapts modularly to the respective conditions. Use existing, normal buildings and simply build a secure data center inside. You save on new construction and have high investment security. The rooms can be converted, dismantled or relocated at any time.

The sandwich panels with steel sheet box construction have a heat-insulating and non-combustible core. The panel thickness for walls and ceiling is approx. 100 mm.

Quartzite Room outside

Features

 

  • Suitable for cables and cable bundles.
  • Customer opening and closing.
  • Easy installation and maintenance.
  • Fully functional immediately after installation.
  • No service costs for cable bulkheads.
  • Easy post-installation of additional cables.
  • Suitable for frequent cable replacement.
  • No dirt accumulation.

New: Optional cable bulkhead system for particularly easy, customer-side cable routing.

Cable bulkhead system of a data center
  • different overpressure dampers depending on room dimensions
  • Overpressure flap FK-EU-0/DE/200x200x500/ES/A0/Z38DV - 6 bar
  • Overpressure flap FK-EU-0/DE/250x250x500/ES/A0/Z38DV - 6 bar
  • Overpressure flap FK-EU-0/DE/350x350x500/ES/A0/Z38DV - 6 bar
  • Overpressure flap FK-EU-0/DE/400x400x500/ES/A0/Z38DV - 6 bar
  • Overpressure flap FK-EU-0/DE/450x450x500/ES/A0/Z38DV - 6 bar
  • aeration and deaeration FK-EU-0/DE/200x200x500/ES/A0/Z43 - spring return actuator 230V
  • Air supply and exhaust FK-EU-0/DE/300x300x500/ES/A0/Z43 - spring return actuator 230V
  • aeration and deaeration FK-EU-0/DE/350x350x500/ES/A0/Z43 - spring return drive 230V

Door system, single leaf

Sizes: 2080x1037 mm and 2174x1162 mm
Lock: Electonic or mechanical

T90 / RC2

  • IT door system T90 / DIN Left / RC2 / 3-sided / E-lock
  • IT door system T90 / DIN Right / RC2 / 3-sided / E-lock
  • IT door system T90 / DIN left / RC2 / 4-sided / E-lock
  • IT door system T90 / DIN right / RC2 / 4-sided / E-lock

T90 / RC3

  • IT door system T90 / DIN Left / RC3 / 3-sided / E-lock
  • IT door system T90 / DIN Right / RC3 / 3-sided / E-lock
  • IT door system T90 / DIN left / RC3 / 4-sided / E-lock
  • IT door system T90 / DIN right / RC3 / 4-sided / E-lock

T30 / RC2

  • IT door system T30 / DIN Left / RC2 / 3-sided / E-lock
  • IT door system T30 / DIN Right / RC2 / 3-sided / E-lock

Panic lock according to DIN EN 1125 right.
Door DIN left also possible.

Soft bulkhead without closure and material up to 7 different variants

  • Control cabinet for door control
  • Control cabinet small with panel (for max. 2 electric sliders)
  • Control cabinet small with tableau (for max. 4 electric sliders)
  • Control cabinet small with tableau (for max. 6 electric sliders)
  • Special control cabinet
  • Cable/lines/cable guide, standard
  • Cable/leads/cable routing, halogen-free
  • Potential equalization rail
  • Potential equalization rail

Sizes
Standard dimensions (clear passage): 2130 x 970 mm, 2330 x 970 mm, 2130 x 1270 mm or 2330 x 1270 mm.
All door systems are available with door hinges DIN left or DIN right. Standard door color: Traffic red (RAL 3020). Other passage dimensions and RAL colors on request.
Lock system
With motorized multipoint locking for control via an on-site access control system.
Door closer
The GEZE TS 5000 door closer is standard, but GEZE TS 5000E with electric hold-open and GEZE TS 5000R with electric hold-open and integrated smoke detector are also available.
Contacts
As standard, the door is equipped with two magnetic contacts of VdS class C for condition monitoring.

  • Access control
  • Raised floor
  • Lighting
  • Electrical system control
  • Monitoring systems
  • Server and network cabinets

There is a wide range of equipment options for the DC IT Room.
We will be happy to advise you on the optimum equipment.

Test certificates

 

  • EI90 system test according to EN 1363
  • Burglary protection WK 2 in accordance with EN 1627-1630, door optionally in WK 3
  • Dust protection IP 5x according to EN 60529
  • Protection against standing water (72 hours, 40 cm, maximum 20 drops).
  • humidity
    Extinguishing water protection IP x6 according to EN 60529
  • wifi
    EMC protection (electromagnetic compatibility)

Tests, valences and certifications

  Granite Quartzite 9.3 Quartzite 9.0
CERTIFICATION (fire protection)      
ECB-S certification according to EN 1047-2:2009+A:2013
External quality control in production
External quality control on the construction site
FIRE PROTECTION      
Type-tested according to EN 1047-2, 60 minutes flame treatment plus cooling curve up to 24 hours
System test with compliance with limit values (50 K, 85 % humidity) according to EN 1047-2 over 30 minutes
General test certificate of the building authorities F90
System test EI 90 according to EN 13501-2/EN 1363-1 from outside to inside
System test EI 90 according to EN 13501-2/EN 1363-1 from inside to outside Optional Optional Optional
Component testing (wall/ceiling) EI 180 according to EN 13501-2/EN 1363-1 from outside to inside
Component test (wall/ceiling) EI 120 according to EN 13501-2/EN 1363-1 from outside to inside
Component test (wall/ceiling) EI 120 according to EN 13501-2/EN 1363-1 from inside to outside
BURGLARY PROTECTION      
Certified burglar resistance RC 3 according to EN 1627/1628/1629/1630
System test burglar resistance RC 3 according to EN 1627/1630 Optional Optional
System test burglar resistance RC 2 according to EN 1627/1630
EXPLOSION PROTECTION      
System test explosion resistance EXR 3 according to EN 13123-2/EN 13124-2
FLUE GAS TIGHTNESS      
System test flue gas tightness according to EN 1634-3
DUST AND WATERPROOF      
System test Dust and water tightness IP 56 according to EN 60529
500 mm water column over 72 hours
400 mm water column over 72 hours
SHIELD INSULATION (EMC protection)      
Shielding effectiveness test according to 50147-1
RESISTANCE TO DEBRIS LOADS      
Impact test according to EN 1047-2 (impact energy approx. 3,000 Nm)
Three ball impact according to DIN 4102-2
Further proofs on request.