DC IT Monitoring
Agent 32.2

The data collector

  • Temperature
  • humidity--alt
    Humidity
  • humidity
    Water leakage
  • Fire detection
  • fog
    Smoke detection
  • Access detection
  • plug
    Power monitoring

The basis of all action is information

After all, information leads to knowledge in action. This also applies to data centers. However, two aspects are particularly important for obtaining information here: on the one hand, maximum security and, on the other, flexibility in the form of interface communication and the possibility of integration with existing plant and measurement technologies. The agent offers countless possibilities in a very small space.

It collects the security-related data of the entire IT infrastructure installed in the data centre at the various measuring points. It then uses predefined properties to compare and evaluate actual and target values. The agent sends a fault message to the customer by e-mail or SMS as soon as anomalies occur in the measured parameters. The system also makes all the collected information available via an SNMP interface for additional queries.

Equipment options

  • DCM Extension Expansion unit for Can Port (additional 64 digital potential-free inputs)
  • Hybrid sensor 0 to +50°C / 0 to 100 % humidity for Can Port
  • Analog sensor temperature 0 to +50°C
  • Analog sensor humidity 0 to 100%
  • Smoke detector for Can Port
  • Analog water point sensor
  • Analog water loop sensor
  • Door contact switch
  • I/R motion detector for Can Port
  • Antenna extension 10m
  • Battery slot compartment for backup battery in case of power failure
  • Modbus RTU interface card

Can expansion unit with 64 digital inputs. This allows the monitoring of 64 digital states via network. Each input can be explicitly equipped with its own alarm such as setting a 12 V DC alarm output. The CAN bus distance must not exceed 225 m.

Dimensions: 40.00 x 215.00 x 40.00 mm (H x W x D) without 19" kit
Weight: 0,6kg
Material: housing 1mm sheet steel
Color: RAL 9005
Mounting: wall mounting, table mounting or 19"-mounting
Delivery includes: 1 x 64DI unit, 1 x RJ12 CAN bus cable, 1 xmounting material, 1 x 19"-kit

Inputs/Outputs:

  • CAN port: 2 x RJ12 port for connection to the RMS
  • Digital inputs: 64 x for connection of external devices with DO

Power supply:

  • Voltage: Via CAN
  •  Power consumption: 1 Watt
  •  External ground connection: no

Environmental conditions & degree of protection:

  • Maximum altitude: 0 - 3,000 m
  • Temperature (operating): 0 - 60 °C
  • Temperature (storage): -10 - 85 °C
  • Relative humidity (operating):
  • 5 - 80 % RH, non-condensing
  • Relative humidity (storage):
  • 5 - 80 % RH, non-condensing
Extension of DC IT Monitoring

DC IT Monitoring at a glance: Monitor and manage

The analysis, monitoring and evaluation of alarm and energy data increase the availability and efficiency of your IT infrastructure. DC IT Monitoring monitors your data center with all its devices, analyzes and visualizes the data volumes and alerts the responsible employees if necessary.

Details

Technical data

32 digital potential free inputs (DI)
8 analog sensor inputs RJ12 connector
2 x 12 VDC alarm outputs max. 0.25A
Relay outputs: 8 x relay port NO/NC
1 CAN open port (for Can sensors or extension units)
Redundant power supply: 90-240 V, IEC C14, fine-wire fuse 2 A, power connection via IEC plug
Network connection (RJ45 10/100 Mbit/s)
Configuration via web browser
SNMP Trap & Get
E-mail, SMS
LTE modem with external antenna 5m antenna cable
Dimensions: 44.45 (1U) x 482.6 mm (19") x 120 mm
Operating temperature: 0 to 50 °C (non-condensing)

Delivery content

1 x DCM Agent, incl. redundant 230V power supply & 4G LTE Slot-In Modem
4G LTE antenna with 5m antenna cable
Antenna cable extension 10m
Cable catcher bracket
19 inch rackmount kit
2x C13 power cable
RJ45 network cable 0.5m
quick start guide
Sensors are not included in the standard delivery. They have to be ordered separately.